Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/25/2010 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED. |
| 05/07/2010 |
INSP - FULL |
|
Violation |
1.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN PEDIATRIC HOSPITALIST BATHROOM. |
| 05/07/2010 |
INSP - FULL |
|
Violation |
2.) TFC 703.1.1 SEAL AROUND CONDUIT IN I.S. ROOM NORTH OF PED'S 300'S NURSES STATION. |
| 05/07/2010 |
INSP - FULL |
|
Violation |
3.) TFC 901.6 REPALCE MISSING SPRINKLER HEAD ESCUTCHEON LAUNDRY ROOM OF FAMILY RESOURCES. |
| 05/07/2010 |
INSP - FULL |
|
Violation |
4.) TFC 901.6 OUTSIDE OF PED'S ROOM #214 THERE IS QUICK REPSONSE SPRINKLER HEAD INSTALLED ADJCENT TO A STANDARD RESPONSE HEAD. |
| 05/07/2010 |
INSP - FULL |
|
Violation |
5.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON BY ROOM #210 IN PED'S. |
| 05/07/2010 |
INSP - FULL |
|
Violation |
6.) TFC 605.5 IN E.D. ADMIN. PATIENT RELATIONS CUBICLE THE EXTENSION CORD CANNOT BE USED AS A SUBSTITIUTE FOR PERMANENT WIRING. |
| 05/07/2010 |
INSP - FULL |
|
Violation |
7.) TFC 605.4.2 POWER STIPS ARE "PIGGY BACKED" IN E.D. ADMIN. PRE-HOSPITAL MANAGEMENT OFFICE. |
| 05/07/2010 |
INSP - FULL |
|
Violation |
8.) TFC 315.2.1 STORAGE ON WEST WALL OF E.D. ADMIN. SUPPLY ROOM MUST BE LOWERED TO 18" BELOW THE SPRINKLER HEAD DEFLECTOR. |
| 05/07/2010 |
INSP - FULL |
|
Violation |
9.) TFC 901.6 THERE IS NO SPRINKLER COVERAGE BETWEEN PHYSICIAN'S CHARTING AREA AND TRAUMA ROOMS. |
| 05/07/2010 |
INSP - FULL |
|
Violation |
10.) TFC 901.6 NUMEROUS LIGHT FIXTURE ESCUTCHEONS ARE MISSING ABOVE PHYSICIAN'S CHARTING AREA. |
| 05/07/2010 |
INSP - FULL |
|
Violation |
11.) TFC 901.6 TWO LIGHT FIXTURE ESCUTCHEONS ARE MISSING IN E.R. LOBBY. |
| 05/07/2010 |
INSP - FULL |
|
Violation |
12.) TFC 901.6 OPEN CEILING PENETRATION EXIST AROUND SPRINKLER PIPING BY SNACK MACHINES IN E.R. LOBBY. |
| 05/07/2010 |
INSP - FULL |
|
Violation |
13.) TFC 605.3 STORAGE IS BLOCKING ELECTRICAL PANELS IN CHILDREN'S EMERGENCY CENTER. |
| 05/07/2010 |
INSP - FULL |
|
Violation |
14.) TFC 1011.4 EXIT SIGN BY C.E.C. NURSE'S STATION IS NOT ILLUMINATED. |