Case: T10FR00922

Parcel: 110120960


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T10FR00922

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
06/25/2010 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED.
05/07/2010 INSP - FULL Violation 1.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN PEDIATRIC HOSPITALIST BATHROOM.
05/07/2010 INSP - FULL Violation 2.) TFC 703.1.1 SEAL AROUND CONDUIT IN I.S. ROOM NORTH OF PED'S 300'S NURSES STATION.
05/07/2010 INSP - FULL Violation 3.) TFC 901.6 REPALCE MISSING SPRINKLER HEAD ESCUTCHEON LAUNDRY ROOM OF FAMILY RESOURCES.
05/07/2010 INSP - FULL Violation 4.) TFC 901.6 OUTSIDE OF PED'S ROOM #214 THERE IS QUICK REPSONSE SPRINKLER HEAD INSTALLED ADJCENT TO A STANDARD RESPONSE HEAD.
05/07/2010 INSP - FULL Violation 5.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON BY ROOM #210 IN PED'S.
05/07/2010 INSP - FULL Violation 6.) TFC 605.5 IN E.D. ADMIN. PATIENT RELATIONS CUBICLE THE EXTENSION CORD CANNOT BE USED AS A SUBSTITIUTE FOR PERMANENT WIRING.
05/07/2010 INSP - FULL Violation 7.) TFC 605.4.2 POWER STIPS ARE "PIGGY BACKED" IN E.D. ADMIN. PRE-HOSPITAL MANAGEMENT OFFICE.
05/07/2010 INSP - FULL Violation 8.) TFC 315.2.1 STORAGE ON WEST WALL OF E.D. ADMIN. SUPPLY ROOM MUST BE LOWERED TO 18" BELOW THE SPRINKLER HEAD DEFLECTOR.
05/07/2010 INSP - FULL Violation 9.) TFC 901.6 THERE IS NO SPRINKLER COVERAGE BETWEEN PHYSICIAN'S CHARTING AREA AND TRAUMA ROOMS.
05/07/2010 INSP - FULL Violation 10.) TFC 901.6 NUMEROUS LIGHT FIXTURE ESCUTCHEONS ARE MISSING ABOVE PHYSICIAN'S CHARTING AREA.
05/07/2010 INSP - FULL Violation 11.) TFC 901.6 TWO LIGHT FIXTURE ESCUTCHEONS ARE MISSING IN E.R. LOBBY.
05/07/2010 INSP - FULL Violation 12.) TFC 901.6 OPEN CEILING PENETRATION EXIST AROUND SPRINKLER PIPING BY SNACK MACHINES IN E.R. LOBBY.
05/07/2010 INSP - FULL Violation 13.) TFC 605.3 STORAGE IS BLOCKING ELECTRICAL PANELS IN CHILDREN'S EMERGENCY CENTER.
05/07/2010 INSP - FULL Violation 14.) TFC 1011.4 EXIT SIGN BY C.E.C. NURSE'S STATION IS NOT ILLUMINATED.