Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T10FR00910
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2010 | VIOL - MEANS OF EGRESS | Correction Required | 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____Place appropriate emergency lighting. 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____ Fix, repair, and/or replace all exit signs in order to meet code standards |