Case: T10FR00886

Parcel: 128141430


Addresses:

5235 E 22ND ST

Inspection Status: Violation

Inspection History: INSP - FULL

Date Description Inspector Results Comments
05/03/2010 INSP - FULL Violation Chapter 906, Portable Fire Extinguishers
TFC 906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. (Professional maintenance yearly, manual inspection monthly, affix a tag to the extinguisher with records of these activities.)

_____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.

TFC 605.6 - Unapproved conditions.
Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

_____ Provide covers for missing knock-outs in breaker boxes.

TFC 2703.5.1 Markings.
Individual containers, cartons or packages shall be conspicuously marked or labeled in an approved manner.

_____ "Used Oil" drums

3003.5.3 - Securing compressed gas containers, cylinders and tanks.
Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods:
1. Securing containers, cylinders and tanks to a fixed object with one or more restraints.
2. Securing containers, cylinders and tanks on a cart or other mobile device designed for the movement of compressed gas containers, cylinders or tanks.
3. Nesting of compressed gas containers, cylinders and tanks at container filling or servicing facilities or in seller's warehouses not accessible to the public. Nesting shall be allowed provided the nested containers, cylinders or tanks, if dislodged, do not obstruct the required means of egress.
4. Securing of compressed gas containers, cylinders and tanks to or within a rack, framework, cabinet or similar assembly designed for such use.
Exception: Compressed gas containers, cylinders and tanks in the process of examination, filling, transport or servicing.

_____ Secure all compressed gas tanks in an approved manner.

TFC 2703.2.2.1 - Design and construction.
Piping, tubing, valves, fittings and related components used for hazardous materials shall be in accordance with the following:
1. Piping, tubing, valves, fittings and related components shall be designed and fabricated from materials that are compatible with the material to be contained and shall be of adequate strength and durability to withstand the pressure, structural and seismic stress and exposure to which they are subject

_____ Replace or relocate plastic Intermediate Bulk Container (IBC) which is not designed for prolonged exposure to sun.

TFC 2703.4 - Material Safety Data Sheets.
Material Safety Data Sheets (MSDS) shall be readily available on the premises for hazardous materials regulated by this chapter. When a hazardous substance is developed in a laboratory, available information shall be documented.
Exception: Designated hazardous waste.

_____ Provide MSDS and training.

TFC 2703.7.1 - Smoking.
Smoking shall be prohibited and "No Smoking" signs provided as follows:
1. In rooms or areas where hazardous materials are stored or dispensed or used in open systems in amounts requiring a permit in accordance with Section 2701.5.
2. Within 25 feet (7620 mm) of outdoor storage, dispensing or open use areas.
3. Facilities or areas within facilities that have been designated as totally "no smoking" shall have "No
Smoking" signs placed at all entrances to the facility or area. Designated areas within such facilities where smoking is permitted either permanently or temporarily, shall be identified with signs designating that smoking is permitted in these areas only.
4. In rooms or areas where flammable or combustible hazardous materials are stored, dispensed or used.

_____ Post "NO SMOKING" signs at entrance to rooms where flammable and combustible liquids are used.