Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T10FR00875
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/01/2010 | VIOL - FIRE PROTECTION SYSTEMS | Approved | all violations abated | |
04/30/2010 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 1___ NEED TO SHOW REPORT THAT HOOD SYSTEM HAS BEEN SERVICED WITHIN SIX MONTHS. FIX DEFICIENCIES. 2___ NEED NOZZLES OVER STOVE ON EAST WALL UNDER HOOD SYSTEM FOR PROPER COVERAGE. |
|
04/30/2010 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. 1___ ALL EXTINGUISHERS NEED TO BE TAGGED AND SERVICED |