Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
06/21/2010 VIOL - MEANS OF EGRESS Approved
04/28/2010 VIOL - MEANS OF EGRESS Violation Double keyed lock on door:
1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

______ Remove Keyed dead bolts except front door to office and managers office. [This will not hinder firefighter egress as there is a large glass area on these doors.]
04/28/2010 VIOL - MEANS OF EGRESS Violation Exit signs not lit:

TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated.

_____Fix light in exit signs x2.
04/28/2010 VIOL - MEANS OF EGRESS Violation Emergency lighting:

IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located]

______Fix all inoperative emergency lights.