Case: T10FR00802

Parcel: 110120960


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T10FR00802

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
05/07/2010 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED.
04/23/2010 INSP - FULL Violation 1.) TFC 1008.1.8 HASPS AND LOCKS MUST BE REMOVED FROM DOORS ON PATIENT ROOMS IN UNIT 470. EXIT DOORS SHALL BE READILY OPENABLE FROM THE EGRESS SIDE WITHOUT THE USE OF A KEY OR SPECIAL KNOWLEDGE.
04/23/2010 INSP - FULL Violation 2.) TFC 901.6 REPLACE MISSING ESCUTCHEON IN FIRE ALARM POWER SUPPLY ROOM IN LAB AREA.
04/23/2010 INSP - FULL Violation 3.) TFC 605.5 THE EXTENSION CORD IN USE IN ADMIN ASSISTANT'S OFFICE ( LINDA'S OFFICE) CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING.
04/23/2010 INSP - FULL Violation 4.) TFC 703.1.1 REPAIR CEILING PENETRATION IN IDF ROOM OF LAB.
04/23/2010 INSP - FULL Violation 5.) TFC 703.1.1 SEAL CEILING PENETRATIONS AROUND CONDUIT IN L.I.S. OFFICE IN SOUTHWEST CORNER.
04/23/2010 INSP - FULL Violation 6.) TFC 703.1.1 SEAL WALL PENETRATION IN HISTOLOGY ON EAST WALL BY CLOCK.
04/23/2010 INSP - FULL Violation 7.) TFC 605.6 INSTALL A COVER PLATE ON OUTLET OUTSIDE OF GROSS ROOM IN HISTOLOGY.
04/23/2010 INSP - FULL Violation 8.) TFC 703.1.1 SEAL WALL PENETRATION BY REFRIDGERATOR FOR MORGUE.
04/23/2010 INSP - FULL Violation 9.) TFC 703.1.1 SEAL WALL PENETRATION ON SOUTHWALL OF MORGUE.
04/23/2010 INSP - FULL Violation 10.) TFC 703.1.1 SEAL CEILING PENETRATONS AROUND CONDUIT IN ADMINISTRATION I.S. CLOSET.
04/23/2010 INSP - FULL Violation 11.) TFC 703.1.1 SEAL PENETRATION IN CEILING TILE IN BUSINESS OFFIECE EAST WALL ABOVE THE COPY MACHINES.
04/23/2010 INSP - FULL Violation 12.) TFC 605.5 REMOVE EXTENSION FROM PERMANENT USE IN NORTH EAST CUBICLE AT NORTH WEST DESK OF BUSINESS OFFICES.
04/23/2010 INSP - FULL Violation 13.) TFC 901.6 REPLACE 2 MISSING ESCUTCHEONS IN CRADLE GIFT SHOP.