Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T10FR00802
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/07/2010 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED. | |
04/23/2010 | INSP - FULL | Violation | 1.) TFC 1008.1.8 HASPS AND LOCKS MUST BE REMOVED FROM DOORS ON PATIENT ROOMS IN UNIT 470. EXIT DOORS SHALL BE READILY OPENABLE FROM THE EGRESS SIDE WITHOUT THE USE OF A KEY OR SPECIAL KNOWLEDGE. | |
04/23/2010 | INSP - FULL | Violation | 2.) TFC 901.6 REPLACE MISSING ESCUTCHEON IN FIRE ALARM POWER SUPPLY ROOM IN LAB AREA. | |
04/23/2010 | INSP - FULL | Violation | 3.) TFC 605.5 THE EXTENSION CORD IN USE IN ADMIN ASSISTANT'S OFFICE ( LINDA'S OFFICE) CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING. | |
04/23/2010 | INSP - FULL | Violation | 4.) TFC 703.1.1 REPAIR CEILING PENETRATION IN IDF ROOM OF LAB. | |
04/23/2010 | INSP - FULL | Violation | 5.) TFC 703.1.1 SEAL CEILING PENETRATIONS AROUND CONDUIT IN L.I.S. OFFICE IN SOUTHWEST CORNER. | |
04/23/2010 | INSP - FULL | Violation | 6.) TFC 703.1.1 SEAL WALL PENETRATION IN HISTOLOGY ON EAST WALL BY CLOCK. | |
04/23/2010 | INSP - FULL | Violation | 7.) TFC 605.6 INSTALL A COVER PLATE ON OUTLET OUTSIDE OF GROSS ROOM IN HISTOLOGY. | |
04/23/2010 | INSP - FULL | Violation | 8.) TFC 703.1.1 SEAL WALL PENETRATION BY REFRIDGERATOR FOR MORGUE. | |
04/23/2010 | INSP - FULL | Violation | 9.) TFC 703.1.1 SEAL WALL PENETRATION ON SOUTHWALL OF MORGUE. | |
04/23/2010 | INSP - FULL | Violation | 10.) TFC 703.1.1 SEAL CEILING PENETRATONS AROUND CONDUIT IN ADMINISTRATION I.S. CLOSET. | |
04/23/2010 | INSP - FULL | Violation | 11.) TFC 703.1.1 SEAL PENETRATION IN CEILING TILE IN BUSINESS OFFIECE EAST WALL ABOVE THE COPY MACHINES. | |
04/23/2010 | INSP - FULL | Violation | 12.) TFC 605.5 REMOVE EXTENSION FROM PERMANENT USE IN NORTH EAST CUBICLE AT NORTH WEST DESK OF BUSINESS OFFICES. | |
04/23/2010 | INSP - FULL | Violation | 13.) TFC 901.6 REPLACE 2 MISSING ESCUTCHEONS IN CRADLE GIFT SHOP. |