Case: T10FR00764

Parcel: 115160430


Addresses:

1001 W GRANT RD


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T10FR00764

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
04/19/2010 VIOL - MEANS OF EGRESS Correction Required IFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

_____1. Remove the double keyed locks from the two south doors and replace them with thumb-turn locks.
NOTE: The panic hardware on the south door is not required and can be removed.


________________________________________________
(John E. Bieg, Fire Inspector, Tucson Fire Department)

I, ______________________ have received a copy of this inspection report. (Building Representative)


______________________________
(Captain)


Re-inspection scheduled on or after _____/_____/_____
Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions.


All noted Tucson Fire Code violations have been corrected: _____/_____/_____

______________________
John E. Bieg