Case: T10FR00747

Parcel: 13819038K


Addresses:

525 W VALENCIA RD


Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T10FR00747

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
04/14/2010 VIOL - BUILDING SVCS & SYSTEMS Violation 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment.
_____ Clear area around electrical panels
04/14/2010 VIOL - BUILDING SVCS & SYSTEMS Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage
or physical impact. Extension cords shall be used only with portable appliances.

__Remove/replace all unprotected extension cords being used as permanent wiring.