Case: T10FR00733

Parcel: 13324005F


Addresses:

550 N PANTANO RD


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T10FR00733

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
08/20/2010 VIOL - BUILDING SVCS & SYSTEMS Approved
04/13/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Open wire boxes/ splices / etc.:

TFC2006 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

______Cover wires in an approved manner. [ceiling of community room]

______ Remove wires from community room wall.

______ Replace cover on electrical box and replace "blanks" as needed - in Pool cleaning equipment room.
04/13/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Wires bad on ceiling fan - maint shop:

TFC2006/ 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.

______ Remove fan and all illegal wiring. If replaced, must be wired according to the ECC [Electrical Code].