Case: T10FR00704

Parcel: 117090190


Addresses:

1001 S 6TH AV


Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T10FR00704

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Violation

Date Description Inspector Results Comments
04/07/2010 VIOL - MEANS OF EGRESS Violation 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.To ensure that there is no confusion on the required exiting from the building the following must be completed:
1. A sign stating "NOT AN EXIT" affixed to the interior side of the door. The sign shall consist of letters having a principal stroke of not less than 0.75 inch wide and at least 6 inches high on a contrasting background.
2. A sign stating "THIS DOOR BLOCKED" affixed to the exterior side of the door. The sign shall consist of letters having a principal stroke of not less than 0.75 inch wide and at least 6 inches high on a contrasting background.