Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T10FR00702
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/07/2010 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 904.11.1 Manual system operation. A manual actuation device shall be located at or near a means of egress from the cooking area, a minimum of 10 feet (3048 mm) and a maximum of 20 feet (6096 mm) from the kitchen exhaust system. The manual actuation device shall be located a minimum of 4 feet (1219 mm)and a maximum of 5 feet (1524 mm)above the floor. The manual actuation shall require a maximum force of 40 pounds (178 N) and a maximum movement of 14 inches (356 mm) to actuate the fire suppression system. ___ Clear area in front of manual pull. |
|
04/07/2010 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. | |
04/07/2010 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. ***The hood exhaust and extinguishing systems shall be inspected and tagged. |
|
04/07/2010 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities. |
|
04/07/2010 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 904.1 General. Automatic fire-extinguishing systems, other than automatic sprinkler systems, shall be designed, installed, inspected, tested and maintained in accordance with the provisions of this section and the applicable referenced standards. ___ Replace missing grease filter above grill. |