Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/20/2010 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED. |
| 04/06/2010 |
INSP - FULL |
|
Violation |
1.) TFC 605.3 A 30" WORKING SPACE IS REQUIRED BY THE FIRE CODE TO PROVIDE ACCESS TO ELECTRICAL PANEL IN MECHANICAL ROOM. |
| 04/06/2010 |
INSP - FULL |
|
Violation |
2.) TFC 901.6 REPLACE MISSING CAPS ON FDC IN REAR OF BUILDING. |