Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T10FR00674
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/08/2010 | INSP - FULL | Approved | ||
03/29/2010 | INSP - FULL | Correction Required | 1. _____ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, back-up power shall be supplied: - Main Exit - Southeast exit - South exit 2. _____ 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes: - J-box cover near prep area - J-box above the "Blueprint #1" 3. _____ 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated: - Repair the ceiling ni the prep area (2 ea. breaches in the ceiling) 4. _____ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed: -All fire extinguisghers shall be serviced and tagged Note: A. All Haz Commnunication is up to date B. Satelite accumilation are is maintain in order C. All chemical are stored properly D. In process of name change of C of O |