Case: T10FR00663

Parcel: 12406151B


Addresses:

187 N PARK AV


Inspection Status: Approved

Inspection History: VIOL - INT.FINISH, DEC. MATL'S

Case Number - T10FR00663

Inspection Description - VIOL - INT.FINISH, DEC. MATL'S

Inspection Status - Approved

Date Description Inspector Results Comments
08/25/2010 VIOL - INT.FINISH, DEC. MATL'S Approved ALL VIOLATIONS CORRECTED. JERSEYS REMOVED. NONE HANGING VERTICALLY FROM CEILING. APPROX 10 JERSEYS FLAT AGAINST CEILING. ALL COMBUSTIBLES HAVE BEEN TREATED WITH INSPECTA-SHIELD PURCHASED FROM UNITED FIRE.
03/25/2010 VIOL - INT.FINISH, DEC. MATL'S Violation 807.1 General requirements. In occupancies in Groups A, E,
I and R-1 and dormitories in Group R-2, curtains, draperies,
hangings and other decorative materials suspended from walls
or ceilings shall meet the flame propagation performance criteria
of NFPA 701 in accordance with Section 806.2 or be
noncombustible.

____ALL DECORATIVE MATERIAL MUST BE TREATED WITH A FIRE RETARDANT SPRAY. PROVIDE PROOF/DOCUMENTATION.
03/25/2010 VIOL - INT.FINISH, DEC. MATL'S Violation 807.1.2 Combustible decorative materials. The permissible
amount of decorative materials meeting the flame propagation
performance criteria of NFPA 701 shall not exceed
10 percent of the aggregate area of walls and ceilings.
Exceptions:
1. In auditoriums in Group A, the permissible
amount of decorative material meeting the flame
propagation performance criteria of NFPA 701
shall not exceed 50 percent of the aggregate area of
walls and ceiling where the building is equipped
throughout with an approved automatic sprinkler
system in accordance with Section 903.3.1.1, and
where the material is installed in accordance with
Section 803.4 of the International Building Code.
2. The amount of fabric partitions suspended from
the ceiling and not supported by the floor in Group
B and M occupancies shall not be limited.

____YOU ARE CONSIDERED AN A-2 OCCUPANCY WITH AN OCCUPANT LOAD GREATER THAN 50. YOUR COMBUSTIBLE DECORATIVE MATERIALS SHALL NOT EXCEED 10% OF THE AGGREGATE AREA OF WALLS AND CEILINGS.