Case: T10FR00644

Parcel: 10821324B


Addresses:

1550 E RIVER RD

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
08/27/2010 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED.
03/23/2010 INSP - FULL Violation 1.) TFC 906.2 THE PORTABLE FIRE EXTINGUISHER IN COPY ROOM IS PAST DUE FOR ANNUAL INSPECTION.
03/23/2010 INSP - FULL Violation 2.) TFC 1006.3 EMERGENCY ILLUMINATION UNIT # 29 IS NOT ILLUMINATING.
03/23/2010 INSP - FULL Violation 3.) TFC 315.2.1 STORAGE IN FREEZER MUST BE MAINTAINED 18" BELOW THE SPRINKLER HEAD DEFLECTOR.
03/23/2010 INSP - FULL Violation 4.) TFC 605.5 THE EXTENSION CORD POWERING THE POWER STRIP IN CHEF'S OFFICE CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING.
03/23/2010 INSP - FULL Violation 5.) TFC 703.1.1 SEAL WALL PENETRATION IN AIR HANDLER CLOSET IN KITCHEN.
03/23/2010 INSP - FULL Violation 6.) TFC 703.1.1 SEAL UP CEILING PENETRATIONS IN AIR HANDLER CLOSET IN BAYADA OFFICE ON 2ND FLOOR.
03/23/2010 INSP - FULL Violation 7.) TFC 605.4.2 POWER STRIPS ARE CONNECTED IN SERIES IN LOFT AREA BY COMPUTERS.