Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/27/2010 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED. |
| 03/23/2010 |
INSP - FULL |
|
Violation |
1.) TFC 906.2 THE PORTABLE FIRE EXTINGUISHER IN COPY ROOM IS PAST DUE FOR ANNUAL INSPECTION. |
| 03/23/2010 |
INSP - FULL |
|
Violation |
2.) TFC 1006.3 EMERGENCY ILLUMINATION UNIT # 29 IS NOT ILLUMINATING. |
| 03/23/2010 |
INSP - FULL |
|
Violation |
3.) TFC 315.2.1 STORAGE IN FREEZER MUST BE MAINTAINED 18" BELOW THE SPRINKLER HEAD DEFLECTOR. |
| 03/23/2010 |
INSP - FULL |
|
Violation |
4.) TFC 605.5 THE EXTENSION CORD POWERING THE POWER STRIP IN CHEF'S OFFICE CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING. |
| 03/23/2010 |
INSP - FULL |
|
Violation |
5.) TFC 703.1.1 SEAL WALL PENETRATION IN AIR HANDLER CLOSET IN KITCHEN. |
| 03/23/2010 |
INSP - FULL |
|
Violation |
6.) TFC 703.1.1 SEAL UP CEILING PENETRATIONS IN AIR HANDLER CLOSET IN BAYADA OFFICE ON 2ND FLOOR. |
| 03/23/2010 |
INSP - FULL |
|
Violation |
7.) TFC 605.4.2 POWER STRIPS ARE CONNECTED IN SERIES IN LOFT AREA BY COMPUTERS. |