Case: T10FR00627

Parcel: 116190680


Addresses:

343 W FRANKLIN ST

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
03/23/2010 VIOL - MEANS OF EGRESS Correction Required 1027.5 Illumination emergency power.
The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027.

_____ Fix, repair, or replace the emergency lighting unit(s) in order to meet code standards

1008.1.8.5 Unlatching.
The unlatching of any door or leaf shall not require more than one operation.

_____ The BASEMENT door secondary locking device shall be disabled or replaced to meet code standards. I.E. the lock shall release when twisted from the interior side.

1028.2 Reliability.
Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied.

1028.3 Obstructions.
A means of egress shall be free from obstructions that would prevent its use.

_____ Remove all obstructions hindering the use, the path, or the activity of all egress doors and be sure to always maintain a clear and obstruction free path to your exits. (ATTN: Back office, 1st floor)

1008.1.8 Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

_____ Remove the double-key lock and replace with an approved locking device such as a thumb turn lock on your basement's stairwell gate.

________________________________________________
(Joseph P. Longo, Inspector, Tucson Fire Department)

I, ______________________ have received a copy of this inspection report.
(Building Representative)

____________________________
(Captain)

Re-inspection scheduled on or after ___/___/___
Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions.
Thank you.

Re-inspection passed:

___________________ Passed on: ________
(Joseph P. Longo)