Case: T10FR00593

Parcel: 111060280


Addresses:

2950 N DODGE BL

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
07/06/2010 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.
03/17/2010 INSP - FULL Violation 1.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT IN WEST WING HALLWAY IS NOT LIGHTING.
03/17/2010 INSP - FULL Violation 2.) TFC 1011.4 THE EXIT SIGN IN WEST WING HALLWAY MUST BE ILLUMINATED AT ALL TIMES.
03/17/2010 INSP - FULL Violation 3.) TFC 1006.3 TWO EMERGENCY ILLUMINATION UNITS IN SOUTHWEST HALLWAY ARE NOT ILLUMINATING.
03/17/2010 INSP - FULL Violation 4.) TFC 605.4.3 THE EXTENSION CORD IN BHT STATION CLOSET CANNOT EXTEND THROUGH THE CEILING.
03/17/2010 INSP - FULL Violation 5.) TFC 605.4 THE MULTI-PLUG ADAPTER AT THE BHT STATION IS NOT PERMITTED BY THE FIRE CODE.
03/17/2010 INSP - FULL Violation 6.) TFC 605.5 THE EXTENSION CORD IN ADMINISTRATIVE OFFICE CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING.
03/17/2010 INSP - FULL Violation 7.) TFC 605.5 THE EXTENSION CORD POWERING THE POWER STRIP IN KITCHEN MANAGER'S OFFICE CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING.
03/17/2010 INSP - FULL Violation 8.) TFC 901.6 REMOVE TAPE FROM SPRINKLER HEADS ABOVE FREEZER UNITS.
03/17/2010 INSP - FULL Violation 9.) TFC 901.4.1 SPRINKLER HEADS ARE REQUIRED IN FREEZER UNITS.
03/17/2010 INSP - FULL Violation 10.) TFC 605.5 INSTALL COVER PLATE ON ELECTRICAL JUNCTION BOX ON BACK PORCH BY FREEZER UNITS.
03/17/2010 INSP - FULL Violation 11.) TFC 901.6 GAUGE ON SPRINKLER RISER MUST BE REPLACED EVERY 5 YEARS.
03/17/2010 INSP - FULL Violation 12.) TFC 901.6.2 F/A AND SPRINKLER SYSTEM ANNUAL INSPECTION REPORTS MUST BE SUBMITTED UPON RE-INSPECTION.