Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/06/2010 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. |
| 03/17/2010 |
INSP - FULL |
|
Violation |
1.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT IN WEST WING HALLWAY IS NOT LIGHTING. |
| 03/17/2010 |
INSP - FULL |
|
Violation |
2.) TFC 1011.4 THE EXIT SIGN IN WEST WING HALLWAY MUST BE ILLUMINATED AT ALL TIMES. |
| 03/17/2010 |
INSP - FULL |
|
Violation |
3.) TFC 1006.3 TWO EMERGENCY ILLUMINATION UNITS IN SOUTHWEST HALLWAY ARE NOT ILLUMINATING. |
| 03/17/2010 |
INSP - FULL |
|
Violation |
4.) TFC 605.4.3 THE EXTENSION CORD IN BHT STATION CLOSET CANNOT EXTEND THROUGH THE CEILING. |
| 03/17/2010 |
INSP - FULL |
|
Violation |
5.) TFC 605.4 THE MULTI-PLUG ADAPTER AT THE BHT STATION IS NOT PERMITTED BY THE FIRE CODE. |
| 03/17/2010 |
INSP - FULL |
|
Violation |
6.) TFC 605.5 THE EXTENSION CORD IN ADMINISTRATIVE OFFICE CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING. |
| 03/17/2010 |
INSP - FULL |
|
Violation |
7.) TFC 605.5 THE EXTENSION CORD POWERING THE POWER STRIP IN KITCHEN MANAGER'S OFFICE CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING. |
| 03/17/2010 |
INSP - FULL |
|
Violation |
8.) TFC 901.6 REMOVE TAPE FROM SPRINKLER HEADS ABOVE FREEZER UNITS. |
| 03/17/2010 |
INSP - FULL |
|
Violation |
9.) TFC 901.4.1 SPRINKLER HEADS ARE REQUIRED IN FREEZER UNITS. |
| 03/17/2010 |
INSP - FULL |
|
Violation |
10.) TFC 605.5 INSTALL COVER PLATE ON ELECTRICAL JUNCTION BOX ON BACK PORCH BY FREEZER UNITS. |
| 03/17/2010 |
INSP - FULL |
|
Violation |
11.) TFC 901.6 GAUGE ON SPRINKLER RISER MUST BE REPLACED EVERY 5 YEARS. |
| 03/17/2010 |
INSP - FULL |
|
Violation |
12.) TFC 901.6.2 F/A AND SPRINKLER SYSTEM ANNUAL INSPECTION REPORTS MUST BE SUBMITTED UPON RE-INSPECTION. |