Case: T10FR00572

Parcel: 11711001B


Addresses:

222 N CHURCH AV


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T10FR00572

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
07/19/2010 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.APPROVED.
03/15/2010 INSP - FULL Violation 1.) TFC 605.6 INSTALL A COVER PLATE ON OUTLET ABOVE REFRIDGERATOR IN KITCHEN.
03/15/2010 INSP - FULL Violation 2.) TFC 904.5.1 THE KITCHEN HOOD SYSTEM IS PAST DUE FOR 6 MO. INSPECTION.
03/15/2010 INSP - FULL Violation 3.) TFC 315.2 COMBUSTIBLE MATERIALS TOO CLOSE TO WATER HEATER. KEEP COMPRESSED GAS CYLINDERS AWAY FROM WATER HEATER.
03/15/2010 INSP - FULL Violation 4.) TFC 3003.5.3 SECURE COMPRESSED GAS CYLINDER TO PREVENT FALLING. LOCATED IN WATER HEATER AREA.
03/15/2010 INSP - FULL Violation 5.) TFC 906.2 THE CLASS K EXTINGUISHER IN KITCHEN IS PAST DUE FOR ANNUAL INSPECTION.
03/15/2010 INSP - FULL Violation 6.) TFC 605.4 THE MULTIPLUG ADAPTER IN INFANT ROOM MUST BE REMOVED.
03/15/2010 INSP - FULL Violation 7.) TFC 901.6 HAVE DEFICIENCIES NOTE ON SPRINKLER SYSTEM ANNUAL INSP REPORT REPAIRED.