Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/19/2010 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.APPROVED. |
| 03/15/2010 |
INSP - FULL |
|
Violation |
1.) TFC 605.6 INSTALL A COVER PLATE ON OUTLET ABOVE REFRIDGERATOR IN KITCHEN. |
| 03/15/2010 |
INSP - FULL |
|
Violation |
2.) TFC 904.5.1 THE KITCHEN HOOD SYSTEM IS PAST DUE FOR 6 MO. INSPECTION. |
| 03/15/2010 |
INSP - FULL |
|
Violation |
3.) TFC 315.2 COMBUSTIBLE MATERIALS TOO CLOSE TO WATER HEATER. KEEP COMPRESSED GAS CYLINDERS AWAY FROM WATER HEATER. |
| 03/15/2010 |
INSP - FULL |
|
Violation |
4.) TFC 3003.5.3 SECURE COMPRESSED GAS CYLINDER TO PREVENT FALLING. LOCATED IN WATER HEATER AREA. |
| 03/15/2010 |
INSP - FULL |
|
Violation |
5.) TFC 906.2 THE CLASS K EXTINGUISHER IN KITCHEN IS PAST DUE FOR ANNUAL INSPECTION. |
| 03/15/2010 |
INSP - FULL |
|
Violation |
6.) TFC 605.4 THE MULTIPLUG ADAPTER IN INFANT ROOM MUST BE REMOVED. |
| 03/15/2010 |
INSP - FULL |
|
Violation |
7.) TFC 901.6 HAVE DEFICIENCIES NOTE ON SPRINKLER SYSTEM ANNUAL INSP REPORT REPAIRED. |