Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T10FR00531
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2010 | VIOL - MEANS OF EGRESS | Approved | ||
| 03/10/2010 | VIOL - MEANS OF EGRESS | Violation | Panic Hardware: TFC2006 / 1028.8 [Tucson Fire Code Modifications] Where panic hardware and fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code. ______Remove keyed dead bolt lock and replace with a "blank" on the west door to pool area. Note: The office is a "B" occupancy needing only one door. The front door lock configuration is acceptable. The east door to the pool may have a keyed lock, and be blocked, as it is not a "signed" exit and is not required. This does not pose a hazard to firefighters as they may egress through the glass. |