Case: T10FR00396

Parcel: 13321293B


Addresses:

6639 E BROADWAY BL


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T10FR00396

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
05/10/2010 VIOL - BUILDING SVCS & SYSTEMS Approved
02/24/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Open space in electrical panel:

TFC2006 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.

_____Place an approved "blank" in the space.
02/24/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Blocked electrical panel:

TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment.

______Fix / replace door in front of electrical panel so it can be opened in an approved manner.