Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/08/2010 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED. |
| 02/22/2010 |
INSP - FULL |
|
Violation |
1.) TFC 901.6 CONCEALED SPRINKLER HEAD COVERS ARE PAINTED IN ADULT EAST MEDS ROOM. |
| 02/22/2010 |
INSP - FULL |
|
Violation |
2.) TFC 901.6 IN CLOSET NEXT TO PHARMACY LIGHT FIXTURE IS BLOCKING SPRINKLER COVERAGE. |
| 02/22/2010 |
INSP - FULL |
|
Violation |
3.) TFC 605.4 THE MULTI-PLUG ADAPTER IN BEHAVIORAL HEALTH PROJECT CO-ORDINATOR'S OFFICE IS NOT PERMITTED. |
| 02/22/2010 |
INSP - FULL |
|
Violation |
4.) TFC 605.4 THE MULTI-PLUG ADAPTOR IN JOSHUA EVAN'S OFFICE IS NOT PERMITTED. |
| 02/22/2010 |
INSP - FULL |
|
Violation |
5.) TFC 605.5 THE EXTENSION CORD POWERING LAMP IN JOSHUA EVAN'S OFFICE IS NOT PERMITTED. |
| 02/22/2010 |
INSP - FULL |
|
Violation |
6.) TFC 3003.5.3 TWO OXYGEN BOTTLES ARE NOT SECURED IN ADULT WEST EXAM ROOM. |
| 02/22/2010 |
INSP - FULL |
|
Violation |
7.) TFC 901.6 IN ADULT WEST HANDI-CAPPED SHOWER ROOM THE CONCEALED SPRINKLER HEAD CAP IS PAINTED. |
| 02/22/2010 |
INSP - FULL |
|
Violation |
8.) TFC 605.5 IN TITLE 36 LIAISON'S OFFICE THE EXTENSION CORD POWERING THE REFRIDGERATOR IS NOT PERMITTED. |
| 02/22/2010 |
INSP - FULL |
|
Violation |
9.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN PED'S THERAPY WATING ROOM. |
| 02/22/2010 |
INSP - FULL |
|
Violation |
10.) TFC 605.6 REPLACE BROKEN OUTLET COVER PLATE IN STORAGE CLOSET BY OLD MEDICAL RECORDS ROOM. |
| 02/22/2010 |
INSP - FULL |
|
Violation |
11.) 703.1.1 REPLACE BROKEN CEILING TILES IN I.T. ROOM NEXT TO HEARING SPECIALISI'S OFFICE. |
| 02/22/2010 |
INSP - FULL |
|
Violation |
12.) TFC 605.5 THE EXTENSION CORD POWERING COFFEE MAKER IN H.R. VICE PRESIDENT'S OFICE IS NOT PERMITTED. |
| 02/22/2010 |
INSP - FULL |
|
Violation |
13.) TFC 315.2.1 MAINTAIN STORAGE 2 FEET FROM CEILING IN COPY ROOM BY VICE PERSIDENT'S OFFICE. |