Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/24/2010 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED. |
| 02/17/2010 |
INSP - FULL |
|
Violation |
1.) TFC 605.5 EXTENSION CORD POWERING WINDOW A/C IN OFFICE CANOT BE A SUBSTITUTE FOR PERMANENT WIRING. |
| 02/17/2010 |
INSP - FULL |
|
Violation |
2.) TFC 605.4 THE MULTI- PLUG ADAPTER IN INFANT ROOM IS NOT PERMITTED. |
| 02/17/2010 |
INSP - FULL |
|
Violation |
3.) TFC 605.5 THE EXTENSION CORD POWERING THE REFRIDGERATOR IN SOUTH INFANT ROOM IS NOT PERMITTED. |
| 02/17/2010 |
INSP - FULL |
|
Violation |
4.) TFC 605.5 THE EXTENSION CORD POWERING THE REFRIDGERATOR ON PORCH OUTSIDE OF INFANT ROOM IS NOT PERMITTED. |
| 02/17/2010 |
INSP - FULL |
|
Violation |
5.) TFC 605.4 THE MULIT-PLUG ADAPTER IN OUTLET IN THE KITCHEN IS NOT PERMITTED. |
| 02/17/2010 |
INSP - FULL |
|
Violation |
6.) TFC 605.5 THE EXTENSION CORD IN KITCHEN IS NOT PERMITTED. |
| 02/17/2010 |
INSP - FULL |
|
Violation |
7.) TFC 901.6.2 THE F/A SYSTEM MUST BE INSPECTED ANNUALLY. THE INSPECTION REPORT MUST BE MAINTAINED ON THE PREMISES. |