Case: T10FR00336

Parcel: 14115355B

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T10FR00336

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
02/23/2010 INSP - FULL Approved
02/09/2010 INSP - FULL Correction Required _____ 605.5 Extension Cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
-OPERATION ROOM
02/09/2010 INSP - FULL Correction Required _____ 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied
02/09/2010 INSP - FULL Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.