Case: T10FR00335

Parcel: 14115355B

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T10FR00335

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
02/23/2010 INSP - FULL Approved
02/09/2010 INSP - FULL Correction Required _____ 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
- PLACE BLANKS IN THE ELECTRICAL PANEL IN THE RISER ROOM
02/09/2010 INSP - FULL Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
- SERVICE FIRE EXTINGUISHERS ANNUALLY. LAST 1996 (4 EACH)
02/09/2010 INSP - FULL Correction Required _____ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, back-up power shall be supplied
- Provide back up power supply for all required exit illumination IN STORAGE AREA 2 EACH