Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T10FR00297
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/15/2010 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED. | |
| 02/08/2010 | INSP - FULL | Violation | 1.) TFC 901.6 LOWER CURTAINS COVERING RECORDS IN RECORDS ROOM TO MAINTAIN 18" SPACE AT TOP. | |
| 02/08/2010 | INSP - FULL | Violation | 2.) TFC 901.6 TRIM CORNER OF CEILING TILE IN RECORDS ROOM SO THAT IT FITS IN PLACE PROPERLY. | |
| 02/08/2010 | INSP - FULL | Violation | 3.) TFC 605.6 INSTALL COVER PLATE ON OUTLET IN MARY'S S'S. OFFICE. | |
| 02/08/2010 | INSP - FULL | Violation | 4.) TFC 1006.3 SERVICE EMERGENCY ILLUMINATION UNIT IN LIBRARY SO THAT IT OPERATES PROPERLY. | |
| 02/08/2010 | INSP - FULL | Violation | 5.) TFC 316.2 CONNECT CLOTHES DRYER VENTS AND ROUTE TO OUTSIDE TO PREVENT BUILD UP OF LINT IN DRYER ROOM. | |
| 02/08/2010 | INSP - FULL | Violation | 6.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN BEDROOM OF HOUSE 5. | |
| 02/08/2010 | INSP - FULL | Violation | 7.) TFC 901.6.2 HAVE FIRE ALARM SYSTEM INSPECTED AND MAINTAIN REPORT ON PREMISES. NOTE: SPRINKLER SYSTEM ANNUAL REPORT WAS SUBMITTED. FIRE DRILL RECORDS ARE IN COMPLIANCE. |