Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
02/08/2010 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.1 Abatement of electrical hazards.
Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used… Electrical blanks shall be placed in all open spaces within any electrical panel or box.

_____ repair damaged power outlet

605.3 Working space and clearance
A working space of not less than 30 inches in width, 36 inches in depth, and 78 inches in height shall be provided in front of electrical service equipment. Where the service equipment is wider than 30 inches, working space shall be no less than the width of the equipment. No storage of any kind shall be located within the designated working space.

_____ Maintain proper working space around all electrical panels according to code.

605.4.1 Power tap design
Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL 1363.

_____Use approved multi-plug addaptors

605.4.2 Power supply
Relocatable power taps shall be directly connected to a permanently installed receptacle.

____Remove daisy-chained multi-plug adapters.