Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T10FR00233
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/28/2010 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | 2 EXIT LIGHTS and 1 Emergency did not operate when tested, Repair the lighting units. INTERNATIONAL FIRE CODE 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. 1006.3. In the event of power supply failure, an emergency electrical system shall automatically illuminate. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. |