Case: T10FR00140

Parcel: 141153540

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T10FR00140

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
02/09/2010 INSP - FULL Approved
01/25/2010 INSP - FULL Correction Required 1. _____ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, back-up power shall be supplied
"Provide back up power supply for all required exit illumination

2. _____ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.

3. _____ 605.5 Extension Cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.