Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T10FR00139
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/16/2010 | INSP - FULL | Approved | abated | |
| 02/09/2010 | INSP - FULL | Correction Required | re check 2/15/2010 1. extinguisher 2. power strips in series |
|
| 01/25/2010 | INSP - FULL | Correction Required | 1. _____ 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. - SOUTH WALL 2. _____ 605.4.1 Power tap design. Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed. -FRONT COUNTER _____ 906.2 General requirements. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. -SERVICE FIRE EXTINGUISHER _____ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, back-up power shall be supplied - back up EMERGENCY LIGHTS SHALL OPERATE |
|
| 01/25/2010 | INSP - FULL | Correction Required |