Case: T10FR00120

Parcel: 105102410


Addresses:

405 E WETMORE RD


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T10FR00120

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/20/2010 VIOL - MEANS OF EGRESS Correction Required IFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

_____1. Remove the double keyed lock from the west door in the back room.
NOTE: Replace it with a thumb-turn deadbolt.
01/20/2010 VIOL - MEANS OF EGRESS Correction Required IFC 1027.3 Exit sign illumination. Exit signs shall be internally or
externally illuminated.

_____1. The east EXIT sign shall be internally illuminated.

_____2. The west EXIT sign shall be internally illuminated.