| 02/16/2010 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
1.) TFC 605.6 INSTALL A COVER PLATE ON OUTLET IN ROOM# 4804 OF CENTRAL BUILDING. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
2.) TFC 605.1 SECURE QUAD OUTLET TO WALL IN AHCCCS OFFICE IN CENTRAL BUILDING. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
3.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED TOGETHER IN SOUTHEAST CORNER OF AHCCCS OFFICE. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
4.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN H.R. RECEPTION AREA. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
5.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN 2804 F IN CENTRAL BUILDING. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
6.) TFC 605.5 EXTENSION CORD POWERING PRINTER IN INFECTION CONTROL OFFICE IS NOT PERMITTED. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
7.) TFC 703.1.1 SEAL PENETRATION IN WALL AND CEILING IN JANITOR'S CLOSET BY 1ST FLOOR STAIRWELL IN CENTRAL BUILDING. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
8.) TFC 703.1.1 REPLACE MISSING CEILING TILE IN KITCHEN ABOVE HOOD. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
9.) TFC 605.6 INSTALL A COVER PLATE ON ELECTRICAL JUNCTION BOX ON EAST WALL OF KITCHEN. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
10.) TFC 901.6.1 INSTALL EXTINGUISHING NOZZLE FOR MIDDLE OPEN FLAME GRILL IN CAFETERIA. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
11.) TFC 1006.3 EMERGENCY ILLUMINATION UNIT IN CAFETERIA DINING AREA IS NOT WORKING. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
12.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN NUTRION MANAGER'S OFFICE. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
13.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN FOOD SERVICES AREA (BACK OFFICE). |
| 01/19/2010 |
INSP - FULL |
|
Violation |
14.) TFC 605.6 INSTALL COVER PLATES ON ALL JUNCITON BOXES IN TUCSON ROOM. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
15.) TFC 605.4.2 POWER STRIPS ARE PIGGY BAKCED IN LINEN ROOM AT BOTH COMPUTER WORK STATIONS. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
16.) TFC 315.2.1 STORAGE MUST BE MAINTAINED 18" BELOW THE SPRINKLER HEAD DEFLECTOR IN PAPER ROOM # 0401. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
17.) TFC 703.1.1 REPLACE MISSING CEILING TILE IN NORTH BUILDING BASEMENT ROOM # 0404. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
18.) TFC 605.5 EXTENSION CORD POWERING MICROWAVE IN CATH LAB BREAK ROOM IS NOT PERMITTED. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
19.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD CAP FOR RECESSED HEAD IN SECLUSION AREA BY ROOM # 2601. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
20.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD CAP FOR RECESSED HEAD IN SECLUSION ROOM # 2401. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
21.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ROOM #3001 OF NORTH BUILDING. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
22.) TFC 901.6 REPLACE MISSING ESCUTCHEON IN HALLWAY BY ROOM # CD4100E IN RESPIRATORY AREA OF WEST BUILDING. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
23. TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ROOM # 4310 IN DIALYSIS. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
24.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ROOM # 4310 IN DIALYSIS. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
26.) TFC 605.6 INSTALL A COVER PLATE ON LIGHT SWITCH AND OUTLET IN ROOM # CD4303. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
27.) TFC 605.4 THE MULIT-PLUG ADAPTER IN ROOM # 3140 ON 3RD FLOOR OF WEST BUILDING MUST BE REMOVED. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
28.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ROOM # 3146 OF WEST BUILDING. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
29.) TFC FIRE RATED DOOR IN FIRE RATED CORRIDOR HAS A BROKEN SELF-CLOSER. ROOM CD 3330. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
30.) TFC 901.6 REPLACE MISSING ESCUTCHEON IN ROOM # 1137 A ON 1ST FLOOR OF WEST BUILDING. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
31.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ROOM # 1564 IN "A" PATIENT CONSULT ROOM IN WEST BUILDING. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
32.) TFC 1006.3 EMERGENCY ILLUMINATION UINT IN PACU RECOVERY IS NOT WORKING. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
33.) TFC 1006.3 EMERGENCY ILLUMINATION UNIT OUTSIDE OF ELEVATOR IN HALLWAY ON 3RD FLOOR SOUTH IS NOT WORKING. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
34.) TFC 1006.3 EMERGENCY ILLUMINATION UINT IN DOCTOR'S SLEEP AREA IN SOUTH BUILDING IS NOT WORKING. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
35.) TFC 605.5 EXTENSION CORD IN PIMA RESEARCH OFFICE CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
36.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ROOM # 1947 B IN REHAB SOUTH BUILDING. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
37.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ADMITTING OFFICE FRONT RECEPTION AREA. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
38.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ADMITTING AREA ROOM # 1903 G. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
39.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ROOM # 1138 IN EMERGENCY DEPT. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
40.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN SECURITY OFFICE. |
| 01/19/2010 |
INSP - FULL |
|
Violation |
41.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN DOCTOR'S DICTATION AREA. |