Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T10FR00095
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/16/2010 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. | |
01/19/2010 | INSP - FULL | Violation | 1.) TFC 605.6 INSTALL A COVER PLATE ON OUTLET IN ROOM# 4804 OF CENTRAL BUILDING. | |
01/19/2010 | INSP - FULL | Violation | 2.) TFC 605.1 SECURE QUAD OUTLET TO WALL IN AHCCCS OFFICE IN CENTRAL BUILDING. | |
01/19/2010 | INSP - FULL | Violation | 3.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED TOGETHER IN SOUTHEAST CORNER OF AHCCCS OFFICE. | |
01/19/2010 | INSP - FULL | Violation | 4.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN H.R. RECEPTION AREA. | |
01/19/2010 | INSP - FULL | Violation | 5.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN 2804 F IN CENTRAL BUILDING. | |
01/19/2010 | INSP - FULL | Violation | 6.) TFC 605.5 EXTENSION CORD POWERING PRINTER IN INFECTION CONTROL OFFICE IS NOT PERMITTED. | |
01/19/2010 | INSP - FULL | Violation | 7.) TFC 703.1.1 SEAL PENETRATION IN WALL AND CEILING IN JANITOR'S CLOSET BY 1ST FLOOR STAIRWELL IN CENTRAL BUILDING. | |
01/19/2010 | INSP - FULL | Violation | 8.) TFC 703.1.1 REPLACE MISSING CEILING TILE IN KITCHEN ABOVE HOOD. | |
01/19/2010 | INSP - FULL | Violation | 9.) TFC 605.6 INSTALL A COVER PLATE ON ELECTRICAL JUNCTION BOX ON EAST WALL OF KITCHEN. | |
01/19/2010 | INSP - FULL | Violation | 10.) TFC 901.6.1 INSTALL EXTINGUISHING NOZZLE FOR MIDDLE OPEN FLAME GRILL IN CAFETERIA. | |
01/19/2010 | INSP - FULL | Violation | 11.) TFC 1006.3 EMERGENCY ILLUMINATION UNIT IN CAFETERIA DINING AREA IS NOT WORKING. | |
01/19/2010 | INSP - FULL | Violation | 12.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN NUTRION MANAGER'S OFFICE. | |
01/19/2010 | INSP - FULL | Violation | 13.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN FOOD SERVICES AREA (BACK OFFICE). | |
01/19/2010 | INSP - FULL | Violation | 14.) TFC 605.6 INSTALL COVER PLATES ON ALL JUNCITON BOXES IN TUCSON ROOM. | |
01/19/2010 | INSP - FULL | Violation | 15.) TFC 605.4.2 POWER STRIPS ARE PIGGY BAKCED IN LINEN ROOM AT BOTH COMPUTER WORK STATIONS. | |
01/19/2010 | INSP - FULL | Violation | 16.) TFC 315.2.1 STORAGE MUST BE MAINTAINED 18" BELOW THE SPRINKLER HEAD DEFLECTOR IN PAPER ROOM # 0401. | |
01/19/2010 | INSP - FULL | Violation | 17.) TFC 703.1.1 REPLACE MISSING CEILING TILE IN NORTH BUILDING BASEMENT ROOM # 0404. | |
01/19/2010 | INSP - FULL | Violation | 18.) TFC 605.5 EXTENSION CORD POWERING MICROWAVE IN CATH LAB BREAK ROOM IS NOT PERMITTED. | |
01/19/2010 | INSP - FULL | Violation | 19.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD CAP FOR RECESSED HEAD IN SECLUSION AREA BY ROOM # 2601. | |
01/19/2010 | INSP - FULL | Violation | 20.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD CAP FOR RECESSED HEAD IN SECLUSION ROOM # 2401. | |
01/19/2010 | INSP - FULL | Violation | 21.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ROOM #3001 OF NORTH BUILDING. | |
01/19/2010 | INSP - FULL | Violation | 22.) TFC 901.6 REPLACE MISSING ESCUTCHEON IN HALLWAY BY ROOM # CD4100E IN RESPIRATORY AREA OF WEST BUILDING. | |
01/19/2010 | INSP - FULL | Violation | 23. TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ROOM # 4310 IN DIALYSIS. | |
01/19/2010 | INSP - FULL | Violation | 24.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ROOM # 4310 IN DIALYSIS. | |
01/19/2010 | INSP - FULL | Violation | 26.) TFC 605.6 INSTALL A COVER PLATE ON LIGHT SWITCH AND OUTLET IN ROOM # CD4303. | |
01/19/2010 | INSP - FULL | Violation | 27.) TFC 605.4 THE MULIT-PLUG ADAPTER IN ROOM # 3140 ON 3RD FLOOR OF WEST BUILDING MUST BE REMOVED. | |
01/19/2010 | INSP - FULL | Violation | 28.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ROOM # 3146 OF WEST BUILDING. | |
01/19/2010 | INSP - FULL | Violation | 29.) TFC FIRE RATED DOOR IN FIRE RATED CORRIDOR HAS A BROKEN SELF-CLOSER. ROOM CD 3330. | |
01/19/2010 | INSP - FULL | Violation | 30.) TFC 901.6 REPLACE MISSING ESCUTCHEON IN ROOM # 1137 A ON 1ST FLOOR OF WEST BUILDING. | |
01/19/2010 | INSP - FULL | Violation | 31.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ROOM # 1564 IN "A" PATIENT CONSULT ROOM IN WEST BUILDING. | |
01/19/2010 | INSP - FULL | Violation | 32.) TFC 1006.3 EMERGENCY ILLUMINATION UINT IN PACU RECOVERY IS NOT WORKING. | |
01/19/2010 | INSP - FULL | Violation | 33.) TFC 1006.3 EMERGENCY ILLUMINATION UNIT OUTSIDE OF ELEVATOR IN HALLWAY ON 3RD FLOOR SOUTH IS NOT WORKING. | |
01/19/2010 | INSP - FULL | Violation | 34.) TFC 1006.3 EMERGENCY ILLUMINATION UINT IN DOCTOR'S SLEEP AREA IN SOUTH BUILDING IS NOT WORKING. | |
01/19/2010 | INSP - FULL | Violation | 35.) TFC 605.5 EXTENSION CORD IN PIMA RESEARCH OFFICE CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING. | |
01/19/2010 | INSP - FULL | Violation | 36.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ROOM # 1947 B IN REHAB SOUTH BUILDING. | |
01/19/2010 | INSP - FULL | Violation | 37.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ADMITTING OFFICE FRONT RECEPTION AREA. | |
01/19/2010 | INSP - FULL | Violation | 38.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ADMITTING AREA ROOM # 1903 G. | |
01/19/2010 | INSP - FULL | Violation | 39.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ROOM # 1138 IN EMERGENCY DEPT. | |
01/19/2010 | INSP - FULL | Violation | 40.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN SECURITY OFFICE. | |
01/19/2010 | INSP - FULL | Violation | 41.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN DOCTOR'S DICTATION AREA. |