Case: T10FR00095

Parcel: 11615088L

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
02/16/2010 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.
01/19/2010 INSP - FULL Violation 1.) TFC 605.6 INSTALL A COVER PLATE ON OUTLET IN ROOM# 4804 OF CENTRAL BUILDING.
01/19/2010 INSP - FULL Violation 2.) TFC 605.1 SECURE QUAD OUTLET TO WALL IN AHCCCS OFFICE IN CENTRAL BUILDING.
01/19/2010 INSP - FULL Violation 3.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED TOGETHER IN SOUTHEAST CORNER OF AHCCCS OFFICE.
01/19/2010 INSP - FULL Violation 4.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN H.R. RECEPTION AREA.
01/19/2010 INSP - FULL Violation 5.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN 2804 F IN CENTRAL BUILDING.
01/19/2010 INSP - FULL Violation 6.) TFC 605.5 EXTENSION CORD POWERING PRINTER IN INFECTION CONTROL OFFICE IS NOT PERMITTED.
01/19/2010 INSP - FULL Violation 7.) TFC 703.1.1 SEAL PENETRATION IN WALL AND CEILING IN JANITOR'S CLOSET BY 1ST FLOOR STAIRWELL IN CENTRAL BUILDING.
01/19/2010 INSP - FULL Violation 8.) TFC 703.1.1 REPLACE MISSING CEILING TILE IN KITCHEN ABOVE HOOD.
01/19/2010 INSP - FULL Violation 9.) TFC 605.6 INSTALL A COVER PLATE ON ELECTRICAL JUNCTION BOX ON EAST WALL OF KITCHEN.
01/19/2010 INSP - FULL Violation 10.) TFC 901.6.1 INSTALL EXTINGUISHING NOZZLE FOR MIDDLE OPEN FLAME GRILL IN CAFETERIA.
01/19/2010 INSP - FULL Violation 11.) TFC 1006.3 EMERGENCY ILLUMINATION UNIT IN CAFETERIA DINING AREA IS NOT WORKING.
01/19/2010 INSP - FULL Violation 12.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN NUTRION MANAGER'S OFFICE.
01/19/2010 INSP - FULL Violation 13.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN FOOD SERVICES AREA (BACK OFFICE).
01/19/2010 INSP - FULL Violation 14.) TFC 605.6 INSTALL COVER PLATES ON ALL JUNCITON BOXES IN TUCSON ROOM.
01/19/2010 INSP - FULL Violation 15.) TFC 605.4.2 POWER STRIPS ARE PIGGY BAKCED IN LINEN ROOM AT BOTH COMPUTER WORK STATIONS.
01/19/2010 INSP - FULL Violation 16.) TFC 315.2.1 STORAGE MUST BE MAINTAINED 18" BELOW THE SPRINKLER HEAD DEFLECTOR IN PAPER ROOM # 0401.
01/19/2010 INSP - FULL Violation 17.) TFC 703.1.1 REPLACE MISSING CEILING TILE IN NORTH BUILDING BASEMENT ROOM # 0404.
01/19/2010 INSP - FULL Violation 18.) TFC 605.5 EXTENSION CORD POWERING MICROWAVE IN CATH LAB BREAK ROOM IS NOT PERMITTED.
01/19/2010 INSP - FULL Violation 19.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD CAP FOR RECESSED HEAD IN SECLUSION AREA BY ROOM # 2601.
01/19/2010 INSP - FULL Violation 20.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD CAP FOR RECESSED HEAD IN SECLUSION ROOM # 2401.
01/19/2010 INSP - FULL Violation 21.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ROOM #3001 OF NORTH BUILDING.
01/19/2010 INSP - FULL Violation 22.) TFC 901.6 REPLACE MISSING ESCUTCHEON IN HALLWAY BY ROOM # CD4100E IN RESPIRATORY AREA OF WEST BUILDING.
01/19/2010 INSP - FULL Violation 23. TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ROOM # 4310 IN DIALYSIS.
01/19/2010 INSP - FULL Violation 24.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ROOM # 4310 IN DIALYSIS.
01/19/2010 INSP - FULL Violation 26.) TFC 605.6 INSTALL A COVER PLATE ON LIGHT SWITCH AND OUTLET IN ROOM # CD4303.
01/19/2010 INSP - FULL Violation 27.) TFC 605.4 THE MULIT-PLUG ADAPTER IN ROOM # 3140 ON 3RD FLOOR OF WEST BUILDING MUST BE REMOVED.
01/19/2010 INSP - FULL Violation 28.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ROOM # 3146 OF WEST BUILDING.
01/19/2010 INSP - FULL Violation 29.) TFC FIRE RATED DOOR IN FIRE RATED CORRIDOR HAS A BROKEN SELF-CLOSER. ROOM CD 3330.
01/19/2010 INSP - FULL Violation 30.) TFC 901.6 REPLACE MISSING ESCUTCHEON IN ROOM # 1137 A ON 1ST FLOOR OF WEST BUILDING.
01/19/2010 INSP - FULL Violation 31.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ROOM # 1564 IN "A" PATIENT CONSULT ROOM IN WEST BUILDING.
01/19/2010 INSP - FULL Violation 32.) TFC 1006.3 EMERGENCY ILLUMINATION UINT IN PACU RECOVERY IS NOT WORKING.
01/19/2010 INSP - FULL Violation 33.) TFC 1006.3 EMERGENCY ILLUMINATION UNIT OUTSIDE OF ELEVATOR IN HALLWAY ON 3RD FLOOR SOUTH IS NOT WORKING.
01/19/2010 INSP - FULL Violation 34.) TFC 1006.3 EMERGENCY ILLUMINATION UINT IN DOCTOR'S SLEEP AREA IN SOUTH BUILDING IS NOT WORKING.
01/19/2010 INSP - FULL Violation 35.) TFC 605.5 EXTENSION CORD IN PIMA RESEARCH OFFICE CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING.
01/19/2010 INSP - FULL Violation 36.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ROOM # 1947 B IN REHAB SOUTH BUILDING.
01/19/2010 INSP - FULL Violation 37.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ADMITTING OFFICE FRONT RECEPTION AREA.
01/19/2010 INSP - FULL Violation 38.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ADMITTING AREA ROOM # 1903 G.
01/19/2010 INSP - FULL Violation 39.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN ROOM # 1138 IN EMERGENCY DEPT.
01/19/2010 INSP - FULL Violation 40.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN SECURITY OFFICE.
01/19/2010 INSP - FULL Violation 41.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN DOCTOR'S DICTATION AREA.