Case: T10FR00081

Parcel: 13323081C


Addresses:

7353 E BROADWAY BL

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
01/13/2010 VIOL - MEANS OF EGRESS Correction Required 1008.1.8 Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

_____ Remove the double-keyed lock and replace with an approved locking device such as, thumb turn lock or panic hardware

1008.1.8.4 Bolt locks.
Manually operated flush bolts or surface bolts are not permitted.

_____ Remove the slide bolt from the ---- egress door, as bolt lock of any kind are not permitted