Case: T10FR00067

Parcel: 133231430


Addresses:

7823 E BROADWAY BL

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
02/16/2010 VIOL - FIRE PROTECTION SYSTEMS Approved
01/12/2010 VIOL - FIRE PROTECTION SYSTEMS Violation Extinguishers not tagged / inspected:

TFC2006/ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.

______ Extinguishers shall be maintained, inspected and tagged [annually] in accordance with this code.
01/12/2010 VIOL - FIRE PROTECTION SYSTEMS Violation Dirty hood:
904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall
state the extent, time and date of cleaning. Such records shall be maintained on the premises.

______ Clean hood and keep it this way.
01/12/2010 VIOL - FIRE PROTECTION SYSTEMS Violation Escutcheons:

903.3.1 Standards. Sprinkler systems shall be designed
and installed in accordance with Sections 903.3.1.1,
903.3.1.2 or 903.3.1.3.

______ Repair or replace above item as necessary.


Thank you,