Case: T10FR00049

Parcel: 13615041A

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T10FR00049

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
02/02/2010 INSP - FULL Approved ALL NOTED TFC VIOLATONS HAVE BEEN CORRECTED. APPROVED.
01/12/2010 INSP - FULL Violation 1.) TFC 901.6 REPLACE MISSING CEILING TILE IN MATH INTERVENTION & READING ROOM.
01/12/2010 INSP - FULL Violation 2.) TFC 605.4.2 POWER STRIPS IN AFTER SCHOOL DIRECTOR'S OFFICE CANNOT BE PIGGY BACKED TOGETHER.
01/12/2010 INSP - FULL Violation 3.) TFC 901.6 A SPRINKLER HEAD IS REQUIRED IN SPED DIRECTOR'S OFFICE.
01/12/2010 INSP - FULL Violation 4.) TFC 605.5 EXTENSION CORD EXTENDING THROUGH CEILING IN ROOM A 5 IS NOT PERMITTED.
01/12/2010 INSP - FULL Violation 5.) TFC 703.1.21 REPAIR WALL PENETRATION IN ROOM A 3.
01/12/2010 INSP - FULL Violation 6.) TFC 605.5 EXTENSION CORD IS NOT PERMITTED TO POWER LAMINATING MACHINE IN 1ST FLOOR COPY ROOM.
01/12/2010 INSP - FULL Violation 7.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN 1ST FLOOR COPY ROOM.
01/12/2010 INSP - FULL Violation 8.) TFC 605.5 A COVER PLATE IS REQUIRED ON OUTLET OUTSIDE OF SPORTS CLOSET.
01/12/2010 INSP - FULL Violation 9.) TFC 901.6 REPLACE MISSING CEILING TILE IN BOY'S LOCKER ROOM.
01/12/2010 INSP - FULL Violation 10.) TFC 703.1.1 PATCH CEILING PENETRATION IN BROOM CLOSET 1ST FLOOR.
01/12/2010 INSP - FULL Violation 11.) 703.1.1 SEAL WALL PENETRATION BY SINK IN GIRL'S LOCKER ROOM.
01/12/2010 INSP - FULL Violation 12.) TFC 1006.3 REPAIR EMEREGENCY ILLUMINATION UNIT IN 8TH GRADE MS. DAVIS' ROOM.
01/12/2010 INSP - FULL Violation 13.) TFC 605.5 EXTENSION CORD IN MR. JONES' 8TH GRADE CLASSROOM.
01/12/2010 INSP - FULL Violation 14.) TFC 605.5 EXTENSION CORD IN MS. WHITAKER'S CLASSROOM CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING.
01/12/2010 INSP - FULL Violation 15.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN KITCHEN BY NORTH WALL.
01/12/2010 INSP - FULL Violation 16.) TFC 906.2 PORTABLE FIRE EXTINGUISHERS IN KITCHEN ARE PAST DUE FOR ANNUAL INSPECTION.
01/12/2010 INSP - FULL Violation 17.) TFC 904.5.1 KITCHEN HOOD EXTINGUISHING SYSTEM IS PAST DUE FOR 6 MO. INSPECTION.
01/12/2010 INSP - FULL Violation 18.) TFC 901.6 REPLACE MISSING ESCUTCHEON IN KITCHEN DRY STORAGE ROOM.
01/12/2010 INSP - FULL Violation 19.) TFC 605.5 EXTENSION CORD IN ROOM # 19 ON 2ND FLOOR CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING.
01/12/2010 INSP - FULL Violation 20.) TFC 1006.3 (2) EMERGENCY ILLUMINATION UNITS IN KINDERGARTEN HALLWAY NOT OPERATING. REPAIR UNITS.
01/12/2010 INSP - FULL Violation 21.) TFC 605.4 MULTI-PLUG ELECTRICAL ADAPTER IN ROOM #18 IS NOT PERMITTED BY THE FIRE CODE.
01/12/2010 INSP - FULL Violation 22.) TFC 605.4.2 POWER STRIPS IN ROOM #6 CANNOT BE PIGGY BACKED TOGETHER.
01/12/2010 INSP - FULL Violation 23.) TFC 605.5 EXTENSION CORD IN ROOM #12 CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING.
01/12/2010 INSP - FULL Violation 24.) TFC 901.6 REPLACE MISSING CEILING TILE IN STORAGE CLOSET OF ROOM #12.
01/12/2010 INSP - FULL Violation 25.) TFC 901.6 (2) EMERGENCY ILLUMINATION UNITS IN 2ND FLOOR 4TH GRADE HALLWAY NOT OPERATING. REPAIR UNITS.
01/12/2010 INSP - FULL Violation 26.) TFC 901.6 REPALCE MISSING ESCUTCHEON IN UPSTAIRS COPY ROOM.
01/12/2010 INSP - FULL Violation 27.) TFC 605.5 EXTENSION CORD IN ROOM #4 CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING.