Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/02/2010 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATONS HAVE BEEN CORRECTED. APPROVED. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
1.) TFC 901.6 REPLACE MISSING CEILING TILE IN MATH INTERVENTION & READING ROOM. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
2.) TFC 605.4.2 POWER STRIPS IN AFTER SCHOOL DIRECTOR'S OFFICE CANNOT BE PIGGY BACKED TOGETHER. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
3.) TFC 901.6 A SPRINKLER HEAD IS REQUIRED IN SPED DIRECTOR'S OFFICE. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
4.) TFC 605.5 EXTENSION CORD EXTENDING THROUGH CEILING IN ROOM A 5 IS NOT PERMITTED. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
5.) TFC 703.1.21 REPAIR WALL PENETRATION IN ROOM A 3. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
6.) TFC 605.5 EXTENSION CORD IS NOT PERMITTED TO POWER LAMINATING MACHINE IN 1ST FLOOR COPY ROOM. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
7.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN 1ST FLOOR COPY ROOM. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
8.) TFC 605.5 A COVER PLATE IS REQUIRED ON OUTLET OUTSIDE OF SPORTS CLOSET. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
9.) TFC 901.6 REPLACE MISSING CEILING TILE IN BOY'S LOCKER ROOM. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
10.) TFC 703.1.1 PATCH CEILING PENETRATION IN BROOM CLOSET 1ST FLOOR. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
11.) 703.1.1 SEAL WALL PENETRATION BY SINK IN GIRL'S LOCKER ROOM. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
12.) TFC 1006.3 REPAIR EMEREGENCY ILLUMINATION UNIT IN 8TH GRADE MS. DAVIS' ROOM. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
13.) TFC 605.5 EXTENSION CORD IN MR. JONES' 8TH GRADE CLASSROOM. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
14.) TFC 605.5 EXTENSION CORD IN MS. WHITAKER'S CLASSROOM CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
15.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN KITCHEN BY NORTH WALL. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
16.) TFC 906.2 PORTABLE FIRE EXTINGUISHERS IN KITCHEN ARE PAST DUE FOR ANNUAL INSPECTION. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
17.) TFC 904.5.1 KITCHEN HOOD EXTINGUISHING SYSTEM IS PAST DUE FOR 6 MO. INSPECTION. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
18.) TFC 901.6 REPLACE MISSING ESCUTCHEON IN KITCHEN DRY STORAGE ROOM. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
19.) TFC 605.5 EXTENSION CORD IN ROOM # 19 ON 2ND FLOOR CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
20.) TFC 1006.3 (2) EMERGENCY ILLUMINATION UNITS IN KINDERGARTEN HALLWAY NOT OPERATING. REPAIR UNITS. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
21.) TFC 605.4 MULTI-PLUG ELECTRICAL ADAPTER IN ROOM #18 IS NOT PERMITTED BY THE FIRE CODE. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
22.) TFC 605.4.2 POWER STRIPS IN ROOM #6 CANNOT BE PIGGY BACKED TOGETHER. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
23.) TFC 605.5 EXTENSION CORD IN ROOM #12 CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
24.) TFC 901.6 REPLACE MISSING CEILING TILE IN STORAGE CLOSET OF ROOM #12. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
25.) TFC 901.6 (2) EMERGENCY ILLUMINATION UNITS IN 2ND FLOOR 4TH GRADE HALLWAY NOT OPERATING. REPAIR UNITS. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
26.) TFC 901.6 REPALCE MISSING ESCUTCHEON IN UPSTAIRS COPY ROOM. |
| 01/12/2010 |
INSP - FULL |
|
Violation |
27.) TFC 605.5 EXTENSION CORD IN ROOM #4 CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING. |