Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - LIFE SAFETY
Case Number - T10FR00038
Inspection Description - INSP - LIFE SAFETY
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/07/2010 | INSP - LIFE SAFETY | Correction Required | 8 facilities / work areas at the EASTSIDE SERVICE CCENTER were inspected with the following deficiencies requiring correction: Bldg #4 Fleet Servs Maintenance Shop; - All 4 exits lights did not operate in the TEST MODE. - The emergency lighting unit in the Locker Room did not illuminate when tested. Repair all the Life Safety lighting units. INTERNATIONAL FIRE CODE (IFC) 1011.5.3 Power source. Exit signs shall be illuminated at all times. NFPA 101, 7.9.2.1. Emergency illumination shall be provided for not less than 1 1/2 hours in the event of failure of the normal lighting. Bldg #5, Welding Shop: The are no emergency lighting units within the facility. Install an Emergency Lighting unit. NFPA 101, 7.9.2.1. Emergency illumination shall be provided for not less than 1 1/2 hours in the event of failure of the normal lighting. All other facilities / areas were code compliant. |