Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2010 | VIOL - MEANS OF EGRESS | Approved | All approved 4/14/2010 - Good Job!! closed. | |
| 01/04/2010 | VIOL - MEANS OF EGRESS | Violation | Exit access, exit, and discharge path blocked: 1027.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency. Security devices affecting means of egress shall be subject to approval of the fire code official. ______ Clear exit path and keep it clear [36" minimum] |
|
| 01/04/2010 | VIOL - MEANS OF EGRESS | Violation | Exit sign not lit: TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. _____Fix light in exit sign. |
|
| 01/04/2010 | VIOL - MEANS OF EGRESS | Violation | Emergency lighting: IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located] ______Fix all inoperative emergency lights. Thank you, |