Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2010 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
| 01/04/2010 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Extinguishers not tagged / inspected: TFC2006/ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ______ Extinguishers shall be maintained, inspected and tagged [annually] in accordance with this code. |
|
| 01/04/2010 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Need "ABC" fire extinguisher: TFC2006/ 904.11.5 Commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. _____ Mount a ABC extinguisher by the back door in an approved manner. |
|
| 01/04/2010 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Hood system: 904.11.6 Operations and maintenance. Commercial cooking systems shall be operated and maintained in accordance with this section. ______ Assure Fire Marshal that the heads cover the fryers in an approved manner. [Note: do not move or re-arrange before cooking] |