Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2010 | VIOL - BUILDING SVCS & SYSTEMS | Approved | ||
| 01/04/2010 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Tape on breakers: TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. _______ Remove tape from breakers. |
|
| 01/04/2010 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Blocked electrical panel: TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. ______Clear area in front of electrical panel in an approved manner. |