Case: T10FR00003

Parcel: 10509546D


Addresses:

90 W RIVER RD


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T10FR00003

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/04/2010 VIOL - MEANS OF EGRESS Correction Required IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system.

_____1. Repair or replace the emergency lighting unit located above the communication board.

_____2. Repair or replace the emergency lighting unit located on the west wall in the sales area.


________________________________________________
(John E. Bieg, Fire Inspector, Tucson Fire Department)

I, ______________________ have received a copy of this inspection report. (Building Representative)


______________________________
(Captain)


Re-inspection scheduled on or after _____/_____/_____
Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions.


All noted Tucson Fire Code violations have been corrected: _____/_____/_____