Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10EL02800
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/11/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
02/08/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
12/15/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE VERIFY WIRING TO CEILING BOXES ALSO VERIFY IF FAN RATED BOXES-WE HAVE 2 SWITCHES 2) WROUGHT IRON IN BEDROOMS TO BE QUICK RELEASE 3) MISSING REQUIRED LIGHTING 4) EXPOSED WIRING AND ILLEGAL SPLICES IN STORAGE ROOM 5) REAR PORCH RECEPT COVER TO BE FOR WET LOCATION 6) USE APPROVED FITTING WITH LB AND SEAL WITH APPROVED DEVICE ABOVE CURRENT CARRING PARTS 7) ONLY ONE GROUNDED CONDUCTOR TO TERMINAL LUG 8) PLEASE VERIFY PERMIT FOR NEW A/C |