Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/14/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED HALL SMOKE DETECTOR 2) NEED CONNECTOR FOR NEW HOOD-ALSO EXPOSED CONDUCTORS IN WALL 3) CORRECTLY LABEL SERVICES AND UNITS 4) USE CORRECT COLOR CONDUCTOR FOR GROUNDED CONDUCTOR 200.6 5) USE BREAKERS LISTED FOR USE BY MANUFACTURE 6) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM BOTTOM OF SUB PANEL 7) LABEL BREAKERS 8) PLEASE VERIFY PERMITS FOR REMODEL WORK INCLUDING CARPORT |