Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/27/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/07/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) VERIFY DERATING OF CONDUCTORS IN RACEWAY 310.15 AND ACROSS ROOF FOR AMBIENT TEMP 310.16 2) USE APPROVED GROUNDING METHODS-SPLIT BOLT RATED FOR 2-CONDUCTORS A LINE AND A TAP |