Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) CLEARANCE AT ROOF TOP PER E3301.3 NOTE 1 |
|
| 12/03/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WIRING FOUND IN HAZARDOUS CONDITION 2) WIRING UNDERSIZED 3) DBL LUGGING NEUTRALS 4) 30 AMP SERVICE OVERLOADED FEEDING 2 RESIDENCES 5) MAIN FEEDER TO REAR UNIT UNDER SIZED 12-2 FEEDING ENTIRE RESIDENCE ON 30 AMP SERVICE. WIRE UNDERSIZED 6) HAVE QUALIFIED ELECTRICIAN BRING ALL WORK TO CODE |