Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/06/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE DISCONNECT NOT RATED FOR OUTDOOR USE-HAS WATER DAMAGE, RUST ON INTERIOR PARTS, SIGNS OF CONDUCTOR OVER HEATING. GUTTER OVER DISCONNECTS NOT RATED FOR OUTDOOR USE. THIS IS A POTENTIAL FIRE AND OR LIFE SAFETY HAZARD. UPGRADE SERVICE IS RECOMMENDED. OBTAIN REQUIRED PERMIT. USE A LICENSED OR QUALIFIED ELECTRIC CONTRACTOR |