Permit: T10EL02594

Parcel: 115200830


Addresses:

1914 W RIVERVIEW ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/08/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/06/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) USE A LISTED J-BOX FOR BRANCH WIRING SPLICES (EXISTING SERVICE STILL INTACT)
2) CANNOT BOND NEUTRALS AND EQUIP. GROUNDS TOGETHER OTHER THAN AT SERVICE EQUIP.
3) INSTALL BRANCH CIRCUIT NEUTRALS, NOT JUST ONE #6