Permit: T10EL02593

Parcel: 120091910


Addresses:

4513 S 6TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/22/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/18/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
11/15/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) POST ADDRESS ON BLDG AND SERVICE
2) FILL UNUSED OPENINGS IN PANEL
3) ONLY ONE NEUTRAL CONDUCTOR PER TERMINAL LUG
4) PLEASE REMOVE UNSAFE-UNSTABLE PORCH STRUCTURE AT REAR OF BLDG
5) GROUNDING ELECTRODE CONDUCTOR MISSING-ALSO WATER BOND
6) PROPERLY INSTALL, SUPPORT BOXES AND CONDUITS ON EXTERIOR OF BLDG
7) NEED ACCESS TO INTERIOR