Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/22/2010 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 11/18/2010 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection :* 1.NEED 2ND GROUND ROD 2.BOND WATER 3.CLEAN EXCESS PAINT FROM RECEPTACAL OR REPLACE 4.FINISH #2,3,5 & 6 PREVIOUS INSPECTION |
|
| 11/15/2010 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |