Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/23/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 12/21/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) USE BREAKERS LISTED FOR USE BY MANUFACTURE 2) GROUNDS CANNOT BE TIED TO NEUTRAL CONDUCTORS-SEPERATE PER 250.24 3) CANNOT USE SHEET METAL THREAD SCREWS FOR GROUNDING 250.8 4) FITTINGS TO BE FOR WET LOCATION 5) 3/4" RACEWAY OVERFILLED 2-#4 AND 1-#6 |
|
| 11/29/2010 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) RECALL AFTER CROSS OVER |