Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T10EL02540

Parcel: 13205015F


Addresses:

3300 E 36TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/11/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/10/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
01/10/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) SUPPORT RISERS WITHIN 3' OF CT CAN
2) LABEL EQUIPMENT FOR HIGH LEG MARKINGS AND ADDRESSING
3) NEED REJECTION PINS FOR FUSES
4) NEED 2ND GROUND ROD
5) PLEASE VERIFY LISTING FOR GROUNDING OF RISER HUBS
6) RECEIVED CHECK #5234 FOR $165.00 AFTER HOURS INSPECTION