Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/10/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 01/10/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) SUPPORT RISERS WITHIN 3' OF CT CAN 2) LABEL EQUIPMENT FOR HIGH LEG MARKINGS AND ADDRESSING 3) NEED REJECTION PINS FOR FUSES 4) NEED 2ND GROUND ROD 5) PLEASE VERIFY LISTING FOR GROUNDING OF RISER HUBS 6) RECEIVED CHECK #5234 FOR $165.00 AFTER HOURS INSPECTION |