Inspection History: ELECTRIC - FINAL

Permit Number - T10EL02497

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/23/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/31/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- ANTIOXIDANT NEEDED ON ALUMINMON CONDUCTORS
- 2 CONDUCTORS UNDER ONE SCREW AT BREAKER NOT ALLOWED
- LABEL CIRCUITS AT PANEL ON COVER
11/29/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) PROTECT WIRES AT ENTRY BACK OF PANEL
2) SECURE PANEL BOARD TO BLDG
3) GROUND RODS TO BE MINIMUM 6' APART
4) LABEL BREAKERS IN PANEL
5) RECALL WHEN READY
11/24/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/08/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
11/04/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) HOME RUNS TO PANEL RUN THRU RACEWAY OR REPLACE EXISTING WALL
2) GFI PROTECT KITCHEN COUNTER RECEPTS
3) SMOKE DETECTORS IN BEDROOMS AND ADJACENT HALL
4) RECEPT AND SWITCH COVER PLATED NEEDED
5) FIXTURES OR COVER CEILING BOXES
6) EGRESS WINDOW NEEDED IN BACK BEDROOM
7) HANDLE NEEDED FOR SECURITY BARS OVER BACK MIDDLE BEDROOM EGRESS WINDOW
8) FAN RATED BOXES IF REPLACING CEILING FANS
9) COVER WITH BLANKS ANY UNUSED CIRCUITS IN PANEL